content loaded
ILSCO PDB-160 Image 1

PWR DIST BLOCK 85AMP TOUCH SAFE ILSCO PDB-160

MFR Part #: PDB-160
SKU #: 1218552
Brand: ILSCO®
UPC: 783669594973
ILSCO® Touch Safe PDB-160 Type PDB Power Distribution Block, 600 VAC, 85 A, 1 Pole, 14 to 4 AWG/16 to 6 AWG Line, 16 to 8 AWG/16 to 6 AWG Load Wire, Copper Alloy
Transparent Cover
For used in confined space
UL 1059 | IEC 60947-7-1 | UL Recognized | CE Certified | VDE Approved | PROP65: it is not known to contain any chemicals associated with this regulation

ILSCO® Touch Safe Power Distribution Block, Type PDB, 600 VAC, 85 A, 1 Pole, 2 Primary Connections/Pole, 5 Secondary Connection/Pole, 14 to 4 AWG/16 to 6 AWG Line, 16 to 8 AWG/16 to 6 AWG Load Wire, Class J/T/RK1/RK5/G/CC Fuse, 100/200 kA Short Circuit, Copper Alloy, Electro Nickel/Tin Plated, Clear, 2.677 in L x 1.929 in W x 1.299 in H Dimensions

Product Details

ILSCO® Touch Safe Power Distribution Block, Type PDB, 600 VAC, 85 A, 1 Pole, 2 Primary Connections/Pole, 5 Secondary Connection/Pole, 14 to 4 AWG/16 to 6 AWG Line, 16 to 8 AWG/16 to 6 AWG Load Wire, Class J/T/RK1/RK5/G/CC Fuse, 100/200 kA Short Circuit, Copper Alloy, Electro Nickel/Tin Plated, Clear, 2.677 in L x 1.929 in W x 1.299 in H Dimensions

Attributes

Amperage Rating85 A
ColorClear
Dimensions2.677 in L x 1.929 in W x 1.299 in H
FinishElectro Nickel/Tin Plated
Fuse TypeClass J/T/RK1/RK5/G/CC
MaterialCopper Alloy
Number of Poles1
Primary Connections/Pole2
Secondary Connection/Pole5
Short Circuit Current Rating100/200 kA
TypeType PDB
Voltage Rating600 VAC
Wire Size14 to 4 AWG/16 to 6 AWG Line, 16 to 8 AWG/16 to 6 AWG Load

Features

  • Manufactured from high strength copper alloy
  • IP20 touch safe protection
  • Compact size
  • High short circuit rated (SCCR)
  • Surface or DIN rail mountable
  • Minimizes risk of electrical shock
  • Aids visual inspection
  • Added protection
  • Provides low contact resistance
  • Easily mounts into new or existing enclosure
  • Connects two or three PDB's, eliminates need for multiple wire inputs
  • (1) 14 to 4 AWG (1) 16 to 6 AWG line, (3) 16 to 8 AWG (2) 16 to 6 AWG load UL rated conductor range
  • (1) 14 to 4 AWG line, (3) 14 to 8 AWG, (2) 14 to 4 AWG load high SCCR conductor range