24V/60V 1 IN GAS VLV HONEYWELL V88A1675

MFR Part #: V88A1675
SKU #: 0482765
Brand: Honeywell
UPC: 400000370934
Honeywell V88A1675 Diaphragm Gas Valve, 1 in, NPT, 1 psi, Aluminum
For atmospheric boilers, commercial water heaters and rooftop heaters applications
UL File No. MH1639 Guide No. YIOZ | CSA 158158-2500005576 (Z21.21-CSA 6.5)

Honeywell Diaphragm Gas Valve, 1 in Nominal, NPT Connection, Number of Ways/Position: 2, 1 psi Pressure, Aluminum, Electrical Connection: 6 in Lead Wire, 0.62 A, 24 VAC, 60 Hz Frequency, 1021 cfh Nominal, 9 W Power Consumption, LP Gas, Natural Gas Fuel, Horizontal Mounting, 32 to 125 deg F, Dimensions: 6-1/16 in H x 4-5/16 in W x 5 in D

Solenoid operated diaphragm valves provide slow opening and fast closing suitable for controlling natural, LP or manufactured gases. They are normally used on atmospheric boilers, commercial water heaters and rooftop heaters.

Product Details

Honeywell Diaphragm Gas Valve, 1 in Nominal, NPT Connection, Number of Ways/Position: 2, 1 psi Pressure, Aluminum, Electrical Connection: 6 in Lead Wire, 0.62 A, 24 VAC, 60 Hz Frequency, 1021 cfh Nominal, 9 W Power Consumption, LP Gas, Natural Gas Fuel, Horizontal Mounting, 32 to 125 deg F, Dimensions: 6-1/16 in H x 4-5/16 in W x 5 in D

Solenoid operated diaphragm valves provide slow opening and fast closing suitable for controlling natural, LP or manufactured gases. They are normally used on atmospheric boilers, commercial water heaters and rooftop heaters.

Attributes

Amperage Rating.62 A
Connection TypeNPT
Dimensions6-1/16 in H x 4-5/16 in W x 5 in D
Electrical Connection6 in Lead Wire
Frequency Rating60 Hz
Fuel TypeLP Gas, Natural Gas
MaterialAluminum
Mounting TypeHorizontal
Nominal Capacity1021 cfh
Nominal Size1 in
Number of Ways/Position2
Power Consumption9 W
Pressure Rating1 psi
Temperature Rating32 to 125 deg F
Voltage Rating24 VAC

Features

  • Close firmly with diaphragm that is both weight and spring loaded
  • 5 s maximum valve opening and 2 s maximum valve closing time
  • Valve closes on power failure and recommended for final shut-off service
  • Set opening time with various sized bleed orifices or adjustable bleed valve
  • Made with cast aluminum in straight through body pattern
  • 1/8-27 NPT bleed and pilot tapping
  • Straight through body pattern