content loaded
MACROMATIC PMD575 Image 1

MACROMATIC PMD575 3 PH 460-600V 10A SPDT MONITOR RELAY

MFR Part #: PMD575
SKU #: 1262592
Brand: MACROMATIC
UPC: 801262040403
MACROMATIC PMD575 3-phase Monitor Relay, 575 VAC, DIN Rail, 10 Amp DPDT relays, phase loss, reversal - fixed, unbalance, over/under voltage - adjustable
UL Listed (cULus, File #E109466) | CE Marked (EN60947-1, EN60947-5-1)

MACROMATIC PMD575 3-phase Monitor Relay, PMD Series, SPDT 5 A at 250V AC Contact Rating, Mechanical Life of 200000 operations, Operating Temp of -25 to 55 deg C, Storage Temp of -25 to 75 deg C, DIN-Rail Mounting, 0.16 lb, 40 VA Power Consumption, 460-600 V Rating

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized after the Restart Delay is completed. Any one of five fault conditions will de-energize the relay after a delay. As standard, re-energization is automatic upon correction of the fault condition. Manual reset is available if an external momentary N.C. switch is connected to terminals 4 and 5. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting.

Product Details

MACROMATIC PMD575 3-phase Monitor Relay, PMD Series, SPDT 5 A at 250V AC Contact Rating, Mechanical Life of 200000 operations, Operating Temp of -25 to 55 deg C, Storage Temp of -25 to 75 deg C, DIN-Rail Mounting, 0.16 lb, 40 VA Power Consumption, 460-600 V Rating

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized after the Restart Delay is completed. Any one of five fault conditions will de-energize the relay after a delay. As standard, re-energization is automatic upon correction of the fault condition. Manual reset is available if an external momentary N.C. switch is connected to terminals 4 and 5. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting.

Attributes

Contact RatingSPDT 5 A at 250V AC
Mounting TypeDIN-Rail
SeriesPMD Series
Mechanical Life200000 operations
Operating Temperature-25 to 55 deg C
Power Consumption40 VA
Storage Temperature-25 to 75 deg C
Voltage Rating460-600 V
Weight.16 lb

Features

  • Universal voltage range of 190-500V AC on PMDU provides the flexibility to cover a variety of applications with one unit (separate 575V-only version available)
  • Protects against phase loss, phase reversal, phase unbalance, undervoltage and overvoltage
  • True RMS voltage measurement ensures accurate sensing across more applications
  • Retains fault indication and continues monitoring all voltages even with a lost phase
  • Manual reset option works with external switch to reset the relay from the outside of enclosure
  • Full fault indication on top of unit for easy troubleshooting
  • Pilot Duty Rating