APPLETON EYM100AL 1 ALMAG 35 SEALING FITTING

MFR Part #: EYM100-AL
SKU #: 1239762
Brand: Appleton®
UPC: 78138160012
Appleton® UNILETS® EYM100-AL Dust-Ignitionproof Explosionproof Raintight Conduit Sealing Fitting With Removable Nipple, 1 in, For Use With IMC/Threaded Rigid Metallic Conduit, Almag 35 Aluminum, Epoxy Powder Coated
Limited
For prevent passage of gases, vapors or flames from one portion of conduit system to another
UL 886 | UL 1203 File No. E10444 | CSA C22.2 No. 30 | CSA 065181 | Class I, Groups A, B, C, D | Class II, Groups E, F, G | Class III

Appleton® UNILETS® Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: EY Series, 1 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Almag 35 Aluminum, Epoxy Powder Coated, 5.42 in L x 1.75 in W

Product Details

Appleton® UNILETS® Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: EY Series, 1 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Almag 35 Aluminum, Epoxy Powder Coated, 5.42 in L x 1.75 in W

Attributes

Country Of OriginMexico
Size1 in
Dimensions5.42 in L x 1.75 in W
FinishEpoxy Powder Coated
MaterialAlmag 35 Aluminum
SeriesEY Series
Suitable For Use WithIMC/Threaded Rigid Metallic Conduit
TypeDust-Ignitionproof Explosionproof Raintight

Features

  • Smooth, rounded integral bushing in each hub to protect conductor insulation
  • Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
  • Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
  • Restrict any explosion to the sealed off enclosure
  • Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
  • Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
  • Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
  • Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
  • Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
  • 25% fill vertical and horizontal conduit sealing fittings for close turning radius