APPLETON APPEYM75 3/4 EXP PROOF SEALING UNILET

MFR Part #: APPEYM75
SKU #: 1245306
Brand: Appleton®
UPC: 78138113537
Appleton® APPEYM75 EY Conduit Sealing Fitting, 3/4 in, For Use With IMC/Threaded Rigid Metallic Conduit, Malleable Iron, Triple-Coated
NEC/CEC Certified Class I, Division 1 and 2, Groups A, B, C, D/Class II, Division 1 and 2, Groups E, F, G/Class III

Appleton®, APPEYM75, Conduit Sealing Fitting, Series: EY, 3/4 in Size, For Use With: IMC/Threaded Rigid Metallic Conduit, Malleable Iron, Triple-Coated, 4.71 in L x 1.38 in W Dimensions

Product Details

Appleton®, APPEYM75, Conduit Sealing Fitting, Series: EY, 3/4 in Size, For Use With: IMC/Threaded Rigid Metallic Conduit, Malleable Iron, Triple-Coated, 4.71 in L x 1.38 in W Dimensions

Attributes

Size3/4 in
Suitable For Use WithIMC/Threaded Rigid Metallic Conduit
Dimensions4.71 in L x 1.38 in W
FinishTriple-Coated
MaterialMalleable Iron
SeriesEY

Features

  • Explosionproof, Dust-Ignitionproof, raintight
  • Prevent passage of gases, vapors or flames from one portion of conduit system to another
  • Restrict any explosion to the sealed off enclosure
  • Prevent pressure piling within conduit system
  • Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
  • Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
  • Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
  • Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit
  • Seal must be located within 18 in of either enclosure
  • Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in Class I, Division 2 locations
  • Smooth, rounded integral bushing in each hub protects conductor insulation
  • Accurately tapped, tapered threads for tight, rigid joints and ground continuity
  • Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
  • Close radius type for sealing vertical or horizontal conduit runs