content loaded
SIEMENS 3RV-1021-4DA10 Image 1

20-25A MOTOR STARTER PROTECTOR SIEMENS 3RV1021-4DA10

MFR Part #: 3RV-1021-4DA10
SKU #: 1011427
Brand: Siemens
UPC: 754554409313
Siemens 3RV-1021-4DA10 Circuit Breaker, 690 VAC, 25 A, 4 kA, 100 kA Interrupt, 3 -Pole
For motor protection
ATEX Compliant | CSA Certified | CCC Certified | CE Certified | UL Listed

Siemens Circuit Breaker, 25 A, 690 VAC, 11 kW, 50/60 Hz, 4 kA, 100 kA Interrupt Rating, 3 Poles, 3 ph Phase, Screw Connection, IP20 Enclosure, (2) 14 to 10 AWG Wire, Universal Mounting, -20 to 60 deg C, 45 mm Width, 96 mm Length, 97 mm Height

The 3RV102, 3RV103 and 3RV104 MSP's can be used as type E self-protected manual combination starters per UL 508 or as components in group installation per NEC 430-53C to turn motors on and off. Each device has built-in heater elements that provide overload protection and magnetic trip elements to protect the motor. When using the 3RV as a manual combination starter, upstream protection is not required. When the 3RV is used as a component in group installation, multiple MSP's can be installed below one circuit breaker to protect its own motor. A contactor can be mounted to the MSP to provide a remotely operated starter.

Product Details

Siemens Circuit Breaker, 25 A, 690 VAC, 11 kW, 50/60 Hz, 4 kA, 100 kA Interrupt Rating, 3 Poles, 3 ph Phase, Screw Connection, IP20 Enclosure, (2) 14 to 10 AWG Wire, Universal Mounting, -20 to 60 deg C, 45 mm Width, 96 mm Length, 97 mm Height

The 3RV102, 3RV103 and 3RV104 MSP's can be used as type E self-protected manual combination starters per UL 508 or as components in group installation per NEC 430-53C to turn motors on and off. Each device has built-in heater elements that provide overload protection and magnetic trip elements to protect the motor. When using the 3RV as a manual combination starter, upstream protection is not required. When the 3RV is used as a component in group installation, multiple MSP's can be installed below one circuit breaker to protect its own motor. A contactor can be mounted to the MSP to provide a remotely operated starter.

Attributes

Amperage Rating: 25 A
Mounting Type: Universal
Number of Poles: 3
Connection Type: Screw
Enclosure Type: IP20
Frequency Rating: 50/60 Hz
Length: 96 mm
Phase: 3 ph
Power Rating: 11 kW
Temperature Rating: -20 to 60 deg C
Voltage Rating: 690 VAC
Width: 45 mm
Wire Size: (2) 14 to 10 AWG

Features

  • Phase failure detection
  • Thermomagnetic design of the overcurrent release and short circuit release
  • No ground fault detection